This installation is faulty because, although one reason for providing a Ground/Earth electrode (at any building) is to provide a "Multiple Earthed Neutral" and an Earth/Ground connection for "Equipment Grounding", it is also to provide "System Grounding" - to dissipate any "Magnetic Pulse" due to a nearby lightning discharge.
Because of this latter requirement, the connection to the Earth/Ground Rod should be no longer than is necessary and contain no unnecessary bends.
The coiling of the conductor in the manner shown, provides an Impedance, which defeats the purpose of this Earth/Ground connection for "System Grounding".
Gefið er leyfi til að afrita, dreifa og/eða breyta þessu skjali samkvæmt Frjálsa GNU Free Documentation License, útgáfu 1.2 eða nýrri, sem gefið er út af Frjálsu hugbúnaðarstofnuninni með engum breytingum þar á. Afrit af leyfinu er innifalið í kaflanum GNU Free Documentation License.http://www.gnu.org/copyleft/fdl.htmlGFDLGNU Free Documentation Licensetruetrue
tilvísun höfundarréttar – Þú verður að tilgreina viðurkenningu á höfundarréttindum, gefa upp tengil á notkunarleyfið og gefa til kynna ef breytingar hafa verið gerðar. Þú getur gert þetta á einhvern ásættanlegan máta, en ekki á nokkurn þann hátt sem bendi til þess að leyfisveitandinn styðji þig eða notkun þína á verkinu.